Protecta III (PRGE - Emergency)
by Chalmit Lighting
Utilising the same reliable design of the standard Protecta III, the emergency version also features intelligent battery and lamp management technology. The luminaire is capable of self-commissioning and routine self-testing to ensure safe and dependable emergency operation. A high emergency output version is also available that increases the lumen output in emergency mode.
- Ability to detect and indicate impending end of emergency lamp life before actual failure.
- Battery management, monitoring and automatic self-test.
- Emergency inhibition and mains power off re-start.
- Automatic lamp de-energisation on opening.
- DTS-01 deluge tested.
- Vibration tested to comply with Lloyds/DNV.
- End of life (EOL) protection to IEC 60079-7.
Type of protection
|
Ex e mb q (Increased safety Encapsulation Powder filling)
|
ATEX Classification
|
Group II Category 2 GD
|
Area Classification
|
Zone 1 and 21 areas to EN 60079-10-1 and EN 60079-10-2 with installation to EN 60079-14
|
Certificate
|
EC Type Examination Certificate Baseefa04ATEX0220
|
Coding
|
EX II 2 GD Ex e mb q IIC T4 Tamb 55°C
|
Enclosure
|
GRP body with polycarbonate cover and brass suspension points
|
Reflector/Geartray
|
White polyester painted zinc coated steel
|
Entry
|
4 x M20 cable entries, 2 at each end
|
Termination
|
Quick release mains terminals - 4 core 4mm² max. conductor with looping and 16A rating through wiring. (6mm² terminations available - /SC option)
|
Installation
|
Two M8 tapped brass inserts located on rear of body
|
Control Gear
|
High Frequency
|
Relamping
|
Quick release diffuser clamp and hinged cover
|
Lampholder
|
G13 (Bi-pin)
|
Burning Position
|
Universal
|
Ingress Protection
|
IP66/67 to EN 60529
|
Electrical Supply
|
220V - 254V 50/60Hz
|
Battery
|
Internal Ni-Cd (6V)
|
Duration
|
90 minutes to EN 60598-2-22
|
Emergency Output
|
50% of one lamp (18W)
25% of one lamp (36W)
|
Std. Cat No.
|
Wattage
|
Lamp
|
TClass
|
T°C (Dust)
|
Ambient °C
|
Weight
|
PRGE/218/BI/EM
|
2x18W
|
T8
|
T4
|
85
|
-20 to +55
|
7.4kg
|
PRGE/236/BI/EM
|
2x36W
|
T8
|
T4
|
85
|
-20 to +55
|
10.9kg
|
PRGE/218/MO/EM
|
2x18W
|
T8
|
T4
|
85
|
-20 to +55
|
7.4kg
|
PRGE/236/MO/EM
|
2x36W
|
T8
|
T4
|
85
|
-20 to +55
|
10.9kg
|
MO – Mono-pin (fa6 Cap) Lamps. Mono-pin Coding: Ex d e mb q IIC.
Options – Suffix to catalogue No.
/120
|
Specific voltage (110/130)
|
/M25
|
M25 cable entries
|
/SC
|
Screwed connection terminal block (up to 6mm² conductors)
|
/SB
|
Stainless steel mounting bush
|
/3P
|
3 phase termination facility (Not available if looping required)
|
/LBE
|
Looping both ends
|
/HEO
|
High emergency output - 45% (36W only)
|
/3H
|
3 hour battery duration*
|
/RI
|
Remote emergency inhibition facility (External switch ordered separately)
|
/SE
|
Spigot entry
|