The Protecta III LED Geartray is a unique solution to upgrade and utilise the very latest LED technology in existing Protecta III fluorescents.
Complete with LED strips and electronic driver, the geartray can be easily retro-fitted into the Protecta III GRP enclosure in a matter of minutes.
The robust enclosure is not compromised as it remains unchanged and all existing cabling and glanding can remain in place offering significant installation cost savings when upgrading to LED.
Type of Protection*
|
Ex e mb q (Increased Safety Encapsulation, Powder filling)
|
ATEX Classification*
|
Group II Category 2 GD
|
Area Classification*
|
Zone 1 and 21 areas to EN 60079-10-1 and EN 60079-10-2 with installation to EN 60079-14
|
Certificate*
|
EC Type Examination Certificate Baseefa04ATEX0220
IECEx Certificate of Conformity
IECEx BAS09.0017
|
Coding*
|
Ex e mb q IIC T4 Gb
Ex tb IIIC T95°C Db IP6X
|
Geartray
|
Aluminium
|
Installation
|
Fix to existing GRP body - refer to IOM
|
Control Gear
|
Electronic Driver
|
Colour Temperature (CCT)
|
6000K (Cool Daylight)
|
Maintenance
|
Components accessible on geartray
|
Battery
|
Internal Ni-Cd (6V) (Emergency only)
|
Emergency Duration
|
90 mins (30% output)
|
Ingress Protection*
|
IP66/67 to EN 60529
|
Surge Protection
|
4kV
|
Electrical Supply
|
220-254V AC, 50/60Hz
|
*Only applicable once installed in Protecta III GRP enclosure
Features
- Highly Energy Efficient
- 120,000 maintenance free hours @ 25°C (L70)
- Simple upgrade of existing fluorescents
Std. Cat No.
|
Delivered Output
|
Power Consumption
|
Ambient °C
|
Weight
|
PRRE/02L/LE
|
2178 lm
|
30W
|
-40 to +55
|
5.0kg
|
PRRE/05L/LE
|
4607 lm
|
60W
|
-40 to +55
|
6.0kg
|
PRRE/02L/LE/EM
|
2178 lm
|
32W
|
-25 to +55
|
6.0kg
|
PRRE/05L/LE/EM
|
4607 lm
|
64W
|
-25 to +55
|
7.5kg
|
Options – Suffix to Catalogue No.
/120
|
Specific voltage (110-130V)
|
/3H
|
3 hour battery duration (15% output)
|
/4K
|
4000K (Neutral White) LED Strips
|
/LT
|
Low temperature version (Emergency ambient becomes -40°C to +55°C)**
|
/LTT
|
Low temperature version with battery temperature regulator (Emergency ambient becomes -40°C to +45°C)
|
*/LT is optional on standard model to minimise ice build-up.